HomeKey FactsSolutionsTechnical infoFAQsNewsAbout UsContact us

Technical

The HCFC phase out is leading to the introduction of a number of new retrofit gases which present a new technical challenge to the marketplace as they are not the same as R22. The following information can assist in deciding on whether to carry out a retrofit and if so what is the best option to go for.

Also please click here to see our refrigerant selection guide

Retrofit gases

There are over 10 different retrofit gases that have come on to the market as replacements for R22, all of them are application specific and can’t function over the temperature range that R22 covered. These gases have the advantage of being designed to run at similar pressures to R22 and work with traditional lubricants providing the option of a simpler retrofit. They are a very viable option for keeping existing systems running after the phase out so long as one is aware of their differences to R22 and potential problem areas

The differences between these gases and R22 are as follows:

  1. The gases have a lower latent heat than R22 – therefore every kg of liquid that goes into the evaporator moves less heat
  2. At the same degree of subcooling as R22 these gases have a higher percentage of flash gas when they go through the expansion valve – therefore less usable liquid reaches the evaporator than with R22
  3. Most of these gases have a higher vapour density than R22 – therefore the compressor can move a higher mass of gas around the system with each stroke than R22

Points 1 and 2 lead to a significant drop in capacity, this is however compensated for by point 3. With these gases it is necessary to open the expansion valve to increase mass flow around the system, the extra mass flow will help make up for the lower latent heats and higher flash gas.

Although increasing the mass flow will compensate for capacity loss, it is unlikely you will achieve the same as R22 and there is generally a slight loss when doing the retrofit along with a slight loss of COP meaning a rise in running costs for the kit. This means that not every system is suitable to be retrofitted with these gases, if the system is in anyway short on capacity the problem will only get worse with these gases and retrofit is not recommended.

Full Retrofit to Mainstream HFC

Doing a full retrofit to a mainstream HFC such as R404A, R507 or R407C can be beneficial from a cost perspective and shouldn’t be discounted. These gases are however not designed to mirror R22 pressures and don’t work with traditional lubricants making the retrofit potentially more complicated.

These gases can really be a benefit with systems that are short on capacity and unsuitable for retrofit to the Isceon or RS retrofit replacements. R407C operates at similar pressures to R22 and exhibits a capacity loss slightly less than that of the Isceon or RS products, while R404A and R507 can provide the same capacity or a capacity increase depending on the operating temperature but work at a higher pressure.

Why not call A-Gas on 01275 376 600 to discuss in more detail?

Further considerations

Seals

When exposed to R22, some seals will absorb some gas and swell slightly; this gas will remain in the seal throughout the retrofit then slowly leach out causing the seals to shrink and cause potential leaks. As a result it is recommended that all seals in the system including Schraeder valves, ball valves, flanges and sight glasses are replaced during retrofit. It is not advised changing any seals in the compressor itself.

Oil return

More complex equipment with external oil return systems can experience oil return issues with these gases if they are used with mineral or alkylbenzene oils. For these systems it is strongly advisable to flush the system with AK Flush or a similar product and replace with POE oil.

Flooded systems

Due to the glide of the Isceon 9 series gases it is not advised that they are used in flooded systems (although some success has been seen in trials with R422D in LPR systems). The RS blends have much lower glides and have proven successful in this application. Why not call A-Gas to discuss if you are looking to retrofit a flooded system? Click here for case study.

Heat recovery

Both the RS and Isceon ranges have significantly lower discharge temperatures than R22, this is good for the compressor but can have an effect on heat recovery systems built into the discharge gases of some systems. Please call A-Gas to discuss if you are retrofitting a system with heat recovery.

Further Information

A-Gas have a very skilled technical team who can assist with your retrofit needs by doing theoretical cycle calculations of how your system will work on the new gas compared with R22. Please give us a call to discuss or return a completed refrigerant selection datasheet

A-Gas refrigerant selection guide

For further information on Isceon products please visit: www.Isceon.com
For further information on RS products please visit: www.refsols.com